Traction alternator rectifier maintenance and test
procedure.
Eleven
cases of rectifier failure have been observed in in last
eighteen months. Details are given below:
|
Loco
No
|
Date
of fail
|
Shed
|
Reason
of failure
|
|
16007
|
3.3.2010
|
N
|
Thermal
switch damaged due to flash over in rectifier panel
|
|
16281
|
24.8.2011
|
M
|
Rectifier
cable damaged
|
|
16518
|
10.7.2011
|
M
|
Rectifier
+ve bus bar insulator punctured
|
|
20074
|
31.3.2010
|
S
|
One
fuse blown
|
|
12178
|
8.4.2010
|
S
|
Two
nos. fuse blown and two nos. diodes short circuited.
|
|
12185
|
30-05-2010
|
S
|
Two nos. diodes short circuited.
|
|
20070
|
03-09-2010
|
S
|
One diode open circuited
|
|
20073
|
01-03-2011
|
S
|
Five fuse blown and three diodes short circuited
|
|
20070
|
10-08-2011
|
S
|
Six diodes open circuited and five nos. Fuse blown
|
|
12176
|
18-08-2011
|
S
|
Rectifier panel fuse blown.
|
Field
visit and interaction with maintenance supervisors revealed gross lack of
knowledge on maintenance and testing of rectifiers. All sheds are directed to
implement the instructions issued below during maintenance of rectifiers.
1. Cleaning:
Dirt causes poor heat dissipation of diodes and
with increasing heat diodes behaviour
changes. Dirt and water vapour provides creepage path causing damage of
rectifier.
Check rectifier panels for dust
and dirt. If dirt presence is more check cyclonic filter condition and
rectifier panel sealing and TA compartment partition wall sealing and take
necessary corrective action.
1.1 Running
schedule cleaning–
Remove the rectifier cover and blow clean
compressed air at approximate 2 kg/cm² to remove dust, dirt and soot
deposition. In case soot/oil deposit is found on glass epoxy
items, heat sink and bus bars, it may be cleaned with the help of cloth soaked
in cleaning solvent. Use long bottle brush cleaner for better accessibility.
1.2
Heavy schedule cleaning For ALCO locomotives :
The complete rectifier panel shall be unloaded in
yearly and above schedule. Clean each part properly with help of cloth soaked
in recommended solvent. (Dober
Chemical Corporation Cleaner 6006, or Turco Chemical Company Steamfas).
For EMD locomotives :
The complete rectifier
panel shall be unloaded in yearly and above schedule. Clean each part properly
with help of cloth soaked in recommended solvent. (Dober Chemical Corporation
Cleaner 6006, or Turco Chemical Company Steamfas).
1.3 CAUTION-
The contact surfaces of the
diodes and heat sink assemblies must not be cleaned with an abrasive material
or wire brush. Such cleaning will destroy the finish and reduce heat rejection
capability.
Water or cleaning solution
allowed to contaminate the arc quenching sand inside the fuse body can cause
the fuse to explode when it is required to isolate a shorted diode.
2. Inspection for Blown FUSE –
For
ALCO locos- Check fuses for any signs of cracks or burning. Flag of the micro
switches on all the fuses should be in closed condition. Check functioning of
micro switch and LED by manual operation.
For
EMD Loco:- check fuses for any signs of cracks or burning. Check fuse
indicating pin. If it protrudes 5mm from the normal position remove the fuse
and check fuse continuity. If the fuse
is found open, check corresponding diodes of the phase.
3.
Inspection
of Snubber circuit
3.1
Snubber
resistors-
Visually
check Snubber resistor for open circuit, overheating and loose terminals. Check
resistance if any abnormality is noticed. Snubber resistors used in
alternator-mounted rectifiers are of rating 20 ohm, 250 watts (for BHEL
rectifiers) and 22 ohm, 50 watts (for HIND rectifiers). Replace the resistor if
it's value is out of the above range or if there is physical damage. Snubber
circuit has been removed in EMD make TA ,but it is still in service in CGL and
DMW make TA 17 in EMD locos. Check resistance and capacitance value during
running schedule.
3.2
Snubber
capacitors-
Visually
check Snubber capacitors for deformation due to short circuit, overheating and
loose terminals. Check capacitance if any abnormality is noticed. Snubber capacitors used in the
alternator-mounted rectifiers are of rating 1.5 MFD 3000V (for BHEL rectifiers)
and 0.47 MFD, 2000V (for Hind Rectifiers). The capacitors should be checked
using an analogue multi meter. A healthy capacitor shall give a kick and show
very high resistance. A capacitor showing short circuit or low resistance (less
than 10 K ohm) should be rejected. The capacitance value should be measured
using a portable capacitance meter. The capacitance value should be within +10%
range. Record of measurement should be kept. Any capacitor showing a reduction
in capacitance by 10% over the last measurement should be rejected.
4. Diode inspection-
If any fuse in the rectifier panel is found open check corresponding
diodes of the phase. To check the diode following test can be followed-
4.1
Diode
resistance check -
Check
forward resistance and reverse resistance of diode.
For
Alco locos if reverse resistance is high (> 100 kΩ) and
forward resistance is low (About 850 Ω) than diode is perfect but if the
reverse resistance is low along with the forward resistance than diode should
be tested for Reverse Voltage Test.
For
EMD locos check the above and if reverse resistance is high
(> 30 kΩ) and forward resistance is low (About 10-20 Ω) than diode is
perfect but if the reverse resistance is low along with the forward resistance
than diode should be tested for Reverse Voltage Test. The 30K-ohm value is for an
individual diode isolated from the circuit. A diode not isolated from the
circuit should register greater than 2K Ohms for EMD locos.
4.2
Reverse
Voltage Test – It should be conducted by connecting diode in reverse direction and
increasing voltage from 0 to 1000 V. Measure correspondingly reverse
leakage current (Ir).
If the Ir is less than 30 mA accept the diode and
if the Ir value is more than 30 mA, reject the diode.
It is better idea to have paired diodes i.e. diodes
having same leakage current in one panel.
4.3
DC Megger Test- Use a hand-cranked or battery
operated Megger to test the
diode. Connect one lead to diode pigtail and other lead to base of diode. If
using a hand crank meter, it is important to crank slowly at first, then
gradually increase the cranking speed to medium. Depending on polarity, the
reading should be zero (blocking) when connected one way, then by reversing
test leads, there should be a definite megger reading of at least one Megohm or
better.
4.4
DC Voltage Test-
Connect a 110-volt incandescent
lamp in series with the suspected diode, and apply 64 vdc (from the locomotive
batteries) to this series connected circuit, then, reverse diode leads and
observe the lamp response.
• If the
diode is good, a light turns ON when the diode is connected one way, and turns
OFF when connected the other way.
•
If the lamp turns
ON both ways, the diode is shorted out.
• If the
lamp remains OFF when the diode is connected both ways, the diode is open
circuit.
4.5
AC Voltage Test-
Connect a 60 to 100-watt,
110-volt incandescent lamp in series with the suspect diode. Apply 110-115
volts, 60-hertz shop power to the circuit, then reverse diode leads and observe
the lamp response.
•
If the diode is
good, the lamp turns ON at about half of its normal light level (half wave
rectification), when the diode is connected in one direction, and is OFF when connected the
other way
•
If the lamp is
close to full light level, the diode is shorted.
•
If the lamp does
not light, the diode is open.
5.
Assembly-
Replace defective diodes with
good diodes of identical polarity, and voltage class (or higher voltage class).
For EMD locos apply a thin coating of
compound 8346481 to the base of the diode hex to cover the surface. Do not
apply on threads. With special diode socket and 0 – 50 ft.-lbs. Torque wrench,
torque diodes to 45 to 47 Nm (33 to 35 ft.-lbs.). Torque diode terminal lug
bolts to between 15 to 18 Nm (11 to 13 ft.-lbs). Tightness
as recommended by OEM should be ensured by using torque wrench.
For ALCO locos apply thin layer of
heat sink compound such as Dow corning make DC340R or equivalent, smear it out
with clean cotton then place diode on heat sink. Place the clamp, insert Allen
screws (M8) then tighten it by torque wrench diagonally setting torque at 12.5 NM.
6.
Replacement-
All
diodes should be replaced after 10 years of service due to thermal/mechanical
degradation.
No comments:
Post a Comment