Circuit Breakers
Circuit
Breakers are one of the critical "safety-valves" of electrical
systems and basic maintenance procedures are essential to maintain maximum
reliability.
It is recommended that following measures may be incorporated
in maintenance practices to improve reliability of circuit breakers
- Visually
inspect the case to determine if any portion indicates overheating;
replace the breaker if overheating indications are found. Use magnifying
glass.
- Check
connections for indications of overheating.
- Check temperature of all circuit
breakers in every trip and replace if goes beyond operating bench mark temperature. (to be decided by taking at least readings of 20) circuit breakers).
- Cycle
the breaker at least five times manually during every schedule
examination.. Observe any reduction of spring tension or bad contact .Even
if once it misses proper contact or power loss / fluctuation is observed
in the circuitry; replace the circuit breaker with a tested circuit
breaker.
- Check
circuit current with clamp meter at circuit breaker output end when loco
is at starting condition during every schedule examination and the current
value achieved must be significantly below the circuit breaker rating
value. Circuit current trend must be observed and in case of any increase
in current value from previous value of same loco or reading observed as
bench mark in other locos, cause of excessive current should be
investigated.
- Check
and record the voltage drop across the breaker using a calibrated digital
voltmeter (capable of reading three places to the right of the decimal
point). Replace all circuit breakers during M24 schedule with test bench
tested new circuit breakers.
·
Remove all
circuit breakers during M12 schedule and test on the test bench before refitting. Effective circuit breaker
maintenance requires well-organized, accurate testing. The ability to
accurately compare circuit breaker tests with previous test results is
essential. It is, therefore, imperative to conduct tests in exactly the same
way and under the same conditions as those conducted earlier. Comparison can
then provide a clear picture of any deviations and changes.
- Thereby indicating whether or not the circuit
breaker should be kept in operation or taken out of service for further
investigation
- The following parameters should be checked
during test bench testing.
1.
Tripping current .The tripping current
must be in the lower side of the MI value.
2.
Temperature rise and tripping time
during testing 150%, 200% and 300% of rated Amp value .It should be in the lower
side of MI value.
3.
Leakage current test.
4.
Freeness check of operating knob
latching mechanism trouble.
5.
MV drop test (also in situ during M4
schedule and above)
6.
Micro Ohm Measurement of Circuit
breakers & Joints: Increased contact resistances of closed circuit breakers
and joints can lead to circuit breaker failure. A periodic check (M2 and above)
of the contact resistance in the system allows this kind of failure to be
prevented.
- The load should be operated at full load for
three hours, or until the breaker reaches normal load temperature; scan
the breaker with an infra red type non-contact thermometer and record the
readings.
Warranty should be
raised against all rejected circuit breakers during schedule checking. RDSO
should be advised with make wise and cause wise failure summary of circuit
breaker failure cases.
You are advised to
closely monitor the implementation of the above instructions and send feed back
to HQ regularly through MCDO format M.MCDO.DSL.3.6.
No comments:
Post a Comment