major
contributors of relay failure are interlock burnt /pitted and operating coil
open circuited .
These failures warrant review of the current maintenance
practices and plan for additional value input beyond existing maintenance paradigm.
Quality
of workmanship and checking must be improved along with proper record keeping
of testing and checking dovetailing Predictive maintenance and trend monitoring relay parameters.
The action plan is given below-
1) Relay interlock burning
and contact surface pitting-
reasons of contact burning or contact
surface damage are –
A)
Timing of drop out and pick up –
When the contacts
are closing, the metal surfaces will collide and hit against each other several
times (bouncing), causing elastic deformation of the contact area and
mechanical destruction of the thin layers.
Again successful
"breaking" of a DC load requires that the relay contacts move to open
with a reasonably high speed. A typical relay will have an accelerating motion
of its armature toward the un energized rest position during drop-out. The
velocity of the armature at the instant of contact opening will play a
significant role in the relay's ability to avoid "tack welding" by
providing adequate force to break any light welds made during the
"make" of a high current resistive load (or one with a high in-rush
current).The more drop out time means more heat generation resulting extensive
damage to contact surface and failure.
The pickup and drop
out time may vary with the following factors-
a)
Defective armature spring (EMD
part no 8373528) due to loss of property ,corrosion etc .
b)
Restricted movement of armature
or contact carrier assly
c)
Loss of property of core
material causes delay in drop out time.
d)
Increase or decrease of
resistance value of operating coil.
Suggestion-
·
Armature spring tension should be checked with digital gravimeter
during overhauling . Spring length (Free length 1.421” and stretch length under 1-1/2 Lbs is 1.646”)should be measured.
·
Armature spring should be checked for any deformity and crack with
illuminated magnifying glass.
·
Armature or contact carrier assly should be checked for wear and
restricted movement. Lubrication should be done if needed,
·
Sometimes core material loses its property and start to behave like
permanent magnet. It should be checked.
·
The coil resistance value should be remained as per MI of
manufacturers and temperature correction chart should be used. If the value
achieved is beyond the limit as per MI it should be discarded.
·
Measurement of contact temperature rise during drop out of the relay
should be done .
B)
Contact failure due to high contact resistance –
The
contacts are the most important element of relay construction. Contact
performance is influenced by contact material,
voltage and current
values applied to
the contacts, the
type of load,
frequency of switching,
ambient atmosphere, form of
contact, contact switching speed and of bounce. Contact resistance is one of
major factor for failure of relays.
Contact resistance mainly depends upon-
·
Contact pressure.
·
Cross sectional area of Contact surface ( Contact matching)
·
Formation of non conductive film of oxides, sulphides and other compounds due to flash over at the time of
contact breaking.
Checking and adjusting relay contact
pressure-
Check the pressure required to open all
normally closed contacts with a
digital gram gauge (5 to 150
gm range).
v Connect the normally closed contacts in
series with a simple low voltage (6 volt) lamp circuit. The reading should be taken at the position
the lamp is de-energized.
v Place the probe of the gauge up close to
the movable contact. A minimum reading of 40 grams is acceptable before contact
opening .With a DC voltage of approximately 2 to 3 volts above the rated pickup
voltage, energize the relay coil.
v Check the pressure required to open all
contacts which close when coil is energized. A minimum reading of 40 grams
should be obtained on this test.
Ø If
the minimum reading of 40 grams is not obtained, the contact brush assembly
will have to be adjusted. Using a
bending tool make gradual adjustments along the length of the contact brush
assembly.
Note- Do not make any
sharp creases or bends in the assembly. When making a correction for a pressure
reading of the normally closed contacts, this will affect the pressure reading
of the contacts that are closed when the coil is energized. Therefore, all contacts
should be rechecked whenever an adjustment is made.
Ø Check the air gap between all normally
open contacts and between open contacts when the relay is energized. This air
gap should be 0.045” minimum.
Ø
Check the
travel gap from the centre of the relay core to the carrier assembly. This
travel gap should be 0.038” minimum.
Typical relay adjusting
tool
c)
Contact surface mismatching-
As we know the resistive value
of any conductor is inversely proportional to cross sectional area of the
conductor ,so the contact surface must be kept as wide as possible to allow
rated current of the circuit to flow though the contact surface without
generating heat. If contact surface reduces ,the resistive characteristic of
the contacts will be come into play and heat will be generated on contact point
resulting pitting or burning of contact surface.
·
Contact surface to be checked minutely for any deformation or
pitting mark.
·
Contact surface matching to be checked by using Prussian blue
washable color.
·
Ensure more than 90% of contact surface matching.
·
Millivolt drop test should be conducted to check contact resistance
on board in running loco and in test room after overhauling.
D)
Formation of non conductive film over contact surface-
The contacts
are practically not
clean because the
surfaces are covered
by thin layers
of low conductivity, semiconductor properties or
even isolating characteristics. These
layers of oxides, sulphides and other compounds will be formed on the surface
of metals by absorption of gas molecules from the ambient atmosphere within a
very short time. The growth of these layers will be slowed down and eventually
stopped as the layer itself prevents further
chemical reaction. The resistance of these layers increases with their
thickness. To get a reliable electrical
contact these layers have to be destroyed.
·
In general relays are designed to wipe out thin surface of non
conductive layers at the time of making contact.
·
If the mv drop test value during test on running locos is found more
than the normal value ,the relay to be removed and dismantled for physical
check up of contact surface.
·
The of movable contact shunt should also be checked for non
integrity and bad soldering.
E) In-rush current-
When an electro-mechanical
relay is de-energized rapidly, the collapsing magnetic field produces a
substantial voltage transient in its effort to disperse the stored energy and
oppose the sudden change of current flow. This relatively large voltage
transient has created EMI, breakdown, and contact tips wear problems. The type
of the load and its inrush current characteristics together with the switching
frequency are important factors that cause contact welding or burning.
The study of
transient voltage and in-rush current reveals following fact with respect to
various loads -
·
Incandescent Lamp Load (
Flasher lamp) -I/IR = 10 to 15 times for 1/3 Sec approx
·
Motor Load (Fuel pump motor and
Turbo lube pump motor)-I/IR = 5 to 10 times for 0.2 to 0.5 Sec
approx
·
Solenoid Load- I/IR
= 10 to 20 times for 0.1 Sec approx
·
Capacitive Load- I/IR=
20 to 40 times for 1/30 Sec approx
(I= Normal load current
and IR=In-Rush current )
Suggestion-
·
Use of Transient suppression component or snubber circuit in
parallel to load –
For suppression of
transient effect based upon the impact on armature motion and optimizing for
normally open contacts, the best suppression method is to use a silicon
transient suppressor diode. This suppressor will have the least effect on relay
dropout dynamics since the relay transient will be allowed to go to a
predetermined voltage level and then permit current to flow with a low
impedance. This results in the stored energy being quickly dissipated by the
suppressor avoiding damage to the relay contact. This technique is already used
in ALCO locos where two freewheeling diodes are used in reverse direction as
arc suppression rectifier across radiator fan contactors R1 and R2 coil to
protect temperature switch contact tips.
2.Operating Coil open circuit failures-
Cause of Operating
coil failure are mainly due to open or short circuit of coil. Failures of relay
occurred due to failure of soldering joint and melting of coil metal due to
excessive heating or insulation damage.
Coil
heating-
A negative effect of
power consumption is the heating of the coil and, in turn, the entire relay.
The coil temperature is a result of:
·
Ambient temperature
·
Self heating (Due to coil Power
consumption= V*I)
·
Induced heating (Due to heat
generated by contact system)
·
Magnetization losses (Due to
eddy currents)
·
Other sources (Due to
components in the vicinity of the relay)
Due to coil heating
coil resistance increases. Resistance at elevated temperature is expressed by Rt
= R0 [(1+ α(T-23)]
Where R0 is the resistance at ambient
temperature (23º C), T is the elevated temperature and α is the temperature
coefficient on winding wire (Copper).
The pick-up coil resistance of copper wire
increases or decreases by 0.4% per degree C. Due to the increase in coil
temperature the coil resistance increases as per the ratio mentioned
above. Hence the pick-up voltage for a
hot coil should be higher to
generate required
pick-up current.
For example if a
copper coil having coil resistance of 400Ω at 20ºC , the resistance value
increases to 432 Ω at 40ºC and pick up voltage must be increased to retain the
same pick up current.
·
So, measurement of coil resistance at ambient temperature Vs
resistance correcting chart to be used for fruitful results.
·
Dry or bad soldering to be checked for if coil resistance value
differs from the value mentioned in MI.
·
Temperature rise during continuous operation and drop out to me
measured and monitored for and deteriorating trend.
·
Color of the coil to be checked for any sign of overheating.
·
Insulation resistance of the coil to be checked with 500V meggar for
deteriorating value.
·
To obtain initial performance throughout life, avoid dropping or hitting the relay
No comments:
Post a Comment